Chiller Plant Case

  • Two 6-yr old chillers under manufacturer service contract. Chiller plant well-equipped with water, temperature and electricity meters but efficiency problems were not identified.
  • Baseline condition: KW/ton > 0.9
  • After energy efficiency improvements: KW/ton <0.7, resulting in
    1. < 20% energy savings
    2. Green Mark recertification achieved
    3. 198,000 KWh per year saved corresponds to SGD 24,000 only in annual energy savings without including maintanence savings.

ClimaCheck, being the core technology, was applied to find

  • Expansion value issues
  • Inadequate Refrigerant Charge
  • Unbalanced water flows
  • Water flowmeter with caliberation problems.

After optimization, the following benefits were achieved

  • Less energy consumption
  • Better reliability
  • Improvement plant for futher savings.